HVLS Ceiling Fan Installation Condition

  1. HVLS ceiling fan is suitable for any building with a ceiling height of 4 meters or more.The spacing of the structural load-bearing columns should be greater than 20% of the fan diameter to be installed.
  2. The load bearing capacity of the roof structure should be more than 150kg.The total weight of the fan equipment is about 125kg (including installation accessories and dynamic load),torque 300N/m,noise level <39db.
  3. The effective coverage area of a single fan is about 30-40 meters,recommend spacing between center points of the two fans: 30-40 meters.
  4. The distance recommended from airfoil to the floor is 6-8m,minimum should not be less than 4 meters.
  5. Make sure that the fan is installed without ceiling lamps or other obstacles.
  6. The recommended distance between the electric control box and the fan (motor) is within 30m.
  7. It’s not recommend for installation at the site with heat sources or lampblack occasion.
Installation Requirement Condition Parameter
Space height≥3.5m
Safe distance between fan blades and plane obstacles≥0.3m
Safe distance between the fan blade and the obstacle above≥0.3m
Safe distance between the fan blade and the obstacle below≥3.0m
Blade diameter2.5m-7.3m
Min. distance between the fan blade and the main beam≥0.5m
Max. distance between the fan blade and the ground≤19m

Facebook
Twitter
LinkedIn

Leave a Reply

Your email address will not be published. Required fields are marked *

3 × 2 =

Just for you

Good quality with favourable price

Sign up to get a discount on your first order

Ask For A Quick Quote

We will contact you within 1 working day, please pay attention to the email with the suffix “@superhvlsfan.com”